Welcome to Guangdong Fleming Electronic Technology Co.,Ltd. !
Back

UES12LCP-SPC-OP

• Meets medical & I.T.E. safety

• 2 MOPP input to output isolation

• Touch current ≤ 10µA

• Energy efficiency level VI

• ≤ 0.075W standby power

• 4V-24V outputs, up to 12W

• Up to 5,000m operating altitude


Model Number Voltage (V) Current (A) Rated PowerRipple & Noise (max) Voltage tolerance Line& Load Regulation Efficiency (Average) Start Up delay
UES12LCP-XXXYYYSPA-OP
UES12LCP-XXXYYYSPC-OP
4.0-5.0 0.01-2.00 10.00W 150 ±7%Line:±1%
Load:±5%
79.01% ≤3s
5.1-6.0 0.01-2.00 12.00W 150 ±7% 80.19% ≤3s
6.1-7.0 0.01-1.71 11.97W 150 ±7% 83.30% ≤3s
7.1-8.0 0.01-1.50 12.00W 150 ±7% 83.30% ≤3s
8.1-9.0 0.01-1.33 11.97W 150 ±5% 83.30% ≤3s
9.1-10.0 0.01-1.20 12.00W 150 ±5% 83.30% ≤3s
10.1-11.0 0.01-1.09 11.99W 150 ±5% 83.30% ≤3s
11.1-12.0 0.01-1.00 12.00W 150 ±5% 83.30% ≤3s
12.1-13.0 0.01-0.94 12.22W 200 ±5% 83.30% ≤3s
13.1-14.0 0.01-0.86 12.04W 200 ±5% 83.30% ≤3s
14.1-15.0 0.01-0.80 12.00W 200 ±5% 83.30% ≤3s
15.1-16.0 0.01-0.75 12.00W 200 ±5% 83.30% ≤3s
16.1-17.0 0.01-0.71 12.07W 200 ±5% 83.30% ≤3s
17.1-18.0 0.01-0.67 12.06W 200 ±5% 83.30% ≤3s
18.1-19.0 0.01-0.63 11.97W 200 ±5% 83.30% ≤3s
19.1-20.0 0.01-0.60 12.00W 200 ±5% 83.30% ≤3s
20.1-21.0 0.01-0.57 11.97W 200 ±5% 83.30% ≤3s
21.1-22.0 0.01-0.55 12.10W 200 ±5% 83.30% ≤3s
22.1-23.0 0.01-0.52 11.96W 200 ±5% 83.30% ≤3s
23.1-24.0 0.01-0.50 12.00W 200 ±5% 83.30% ≤3s    

1.jpg

Notes 

 (*1) Other options are available, please contact our sales representative for details. 

 (*2) Measured at output connector with 20MHz bandwidth and 0.1uF ceramic in parallel with 10uF electrolytic capacitors.

Input Voltage Range

90-264VAC
Frequency Range 47-63Hz
Input Current0.5A at 90VAC
Inrush Current50A max at 240VAC cold start
Touch Leakage Current≤10μA at 264VAC

Dimensions(mm)

71.5(L)  42(W)  19(H)
Weight35g
MTBF>100,000hrs MIL-HDBK-217 at 25℃
Overload120-200% rated output power, auto recovery
Over Voltage120-150% rated output voltage input to reset
Short CircuitTrip and restart (hiccup mode)
Safety Agency / MarkMedicalITE
CB

IEC60601-1

IEC60950-1    
ULANSI/AAMI ES60601-1-
CAN/CSA C22.2 NO. 60601-1
FCC-FCC PART15
EmissonsMedicalITE
ConductedIEC/EN 60601-1-2,CISPR 11EN55032, CISPR 32
RadiatedIEC/EN 60601-1-2,CISPR 11EN55032, CISPR 32
Harmonic CurrentsEN61000-3-2, Class AEN61000-3-2, Class A
Voltage FlickerEN61000-3-3EN61000-3-3
ImmunityIEC/EN 60601-1-2EN55024, CISPR 24
Radiated ImmunityEN61000-4-3

10V/m ,3V/m 80MHz - 2.7GMHz

EFT/BurstEN61000-4-4±2KV on AC port, ±1KV on signal ports
SurgeEN61000-4-5±2KV line to line (different mode) compatible with ±4KV line to line (different mode)
Conducted ImmunityEN61000-4-63Vrms, 6Vrms (0.15MHz-80MHz)
Magnetic FieldEN61000-4-830 A/m

Dips & Interruptions

EN61000-4-110%, 70%, 0% of UT
Dielectric Withstand Voltage

5,656VDC input to output

Insulation Resistance10M Ohms, 500VDC input to output